← All products

HVAC Filters / W-CELL

W-Cell Air Filter

Extended-surface filtration for air handling units.

A W-cell configuration for intermediate air filtration. Ask our team to match the filter to your operating conditions.

Standard models and custom dimensions available. Ask us to match your filtration requirements.

Product overview

What it is and where it fits.

The W-Cell is a deep-pleat intermediate filter with corrugated aluminium separators for the medium-efficiency stage of HVAC systems. Double-folded separator edges protect the media, and epoxy or PU perimeter seals prevent bypass.

Water-resistant micro-glass fibre media is available in 60–65%, 80–85% and 90–95% dust-spot grades, in 150 mm and 292 mm depths, with galvanised steel, aluminium or stainless steel frames in box or flanged formats. Special high-temperature configurations can be discussed.

Filter type
Rigid separator filter (W-Cell)
Media
Water-resistant micro-glass fibre
Dust-spot grades
60–65%, 80–85%, 90–95% (MERV 11–14)
Depths
150 mm and 292 mm
Initial pressure drop (90–95%)
82 Pa (150 mm), 137 Pa (292 mm); final 324 Pa
Frames
Galvanised steel, aluminium, stainless steel; box or flange
Temperature
60 °C standard; high-temperature builds on request

Typical applications

  • Medium-efficiency stage in air handling units
  • Pre-HEPA filtration
  • Warm-air or high-temperature duty (special build)

Construction & performance

Separator construction

A corrugated-separator intermediate filter for HVAC systems. Double-folded aluminum separator edges protect the media. Box and flanged metal frames are available.

Materials & performance

Water-resistant micro-glass fiber media; epoxy or PU perimeter seals; galvanized steel, aluminum or stainless steel frames. Dust-spot grades: 60–65%, 80–85% and 90–95%.

Temperature selection

The standard construction is rated as shown in the operating-condition table. High-temperature constructions are available on request.

Selection guide

How to choose.

01

Rigid filter for demanding duty

Unlike a pocket filter, a W-Cell keeps its shape at variable airflow and in turbulent or humid air.

02

High temperature

The standard assembly is rated 60 °C; ask for the high-temperature construction for hotter air.

Technical data

Specifications & dimensions.

Rated airflow in m³/h, pressure drop in Pa, actual dimensions in mm, nominal sizes in inches. Swipe tables sideways on small screens.

Efficiency & test standard
Dust-spot efficiencyGravimetric efficiencyMERV
90–95%> 99%14
80–85%> 98%13
60–65%> 97%11
Test standard: ASHRAE 52.1-1992 / EN 779MERV: ASHRAE 52.2
High-temperature configurations available on request
Dimensions & performance
Efficiency
(%)
Nominal size
(in)
Actual size
(mm)
Rated airflow
(m³/h)
Pressure drop
(Pa)
Dust-spot efficiencyGravimetric efficiencyInitial pressure dropFinal pressure drop
90–95> 9912 × 24 × 6289 × 595 × 15085082324
24 × 24 × 6595 × 595 × 1501700
12 × 24 × 12289 × 595 × 2921700137
24 × 24 × 12595 × 595 × 2923400
80–85> 9812 × 24 × 6289 × 595 × 15085074324
24 × 24 × 6595 × 595 × 1501700
12 × 24 × 12289 × 595 × 2921700120
24 × 24 × 12595 × 595 × 2923400
60–65> 9712 × 24 × 6289 × 595 × 15085062324
24 × 24 × 6595 × 595 × 1501700
12 × 24 × 12289 × 595 × 2921700102
24 × 24 × 12595 × 595 × 2923400
Materials & operating conditions
TypeSpecification
ConstructionFilter mediaMicro-glass fiber paper
Support materialCorrugated separator
SealantPU BASE
Gasket materialNeoprene rubber
Frame materialMetal frame
Frame typeBox typeSingle flange
Operating conditionsMaximum continuous temperature℃60
Maximum relative humidity%RH100 (non-condensing)

Catalogue values at rated airflow. Test data for your exact configuration is available on request.

Original Yiding catalogue (Chinese) ↗

FAQ

Common questions.

What is a W-Cell filter?

A rigid box filter in which deep pleats of glass-fibre media are separated by corrugated aluminium, giving a large, stable media area for medium-efficiency filtration.

W-Cell or V-Cell?

Both are rigid medium-efficiency filters. The W-Cell uses aluminium separators and suits high-temperature builds; the V-Cell uses lighter mini-pleat panels in a V.

Beyond the catalogue

Your dimensions.
Your filtration requirements.

More models are available on enquiry. Tell us your target dimensions, model reference, media, frame, sealing and filtration requirements.

Discuss this configuration↗