← All products

HVAC Filters / H14 · 70 mm

Double-Guard H14 Mini-Pleat HEPA Filter

1170 × 570 × 70 mm. Dual face guards and black gaskets on both sides.

A shallow glass-fibre HEPA panel with an inward-return aluminium frame, protective mesh on both faces and double-sided gasket sealing. Designed for final-stage clean-air applications with a matching housing.

Standard models and custom dimensions available. Ask us to match your filtration requirements.

Product overview

What it is and where it fits.

This 70 mm-deep H14 panel combines a glass-fibre mini-pleat filter pack with dual face protection and gasket sealing on both sides. The featured size is 1170 × 570 mm, with alternative sizes and configurations available to order.

Efficiency class
H14
Featured size
1170 × 570 × 70 mm
Frame construction
Inward-return aluminium
Protection & sealing
Dual mesh · dual black gaskets

Typical applications

  • Final-stage filtration in compatible cleanroom terminal housings
  • Fan filter units with matching dimensions and available static pressure
  • Clean benches and controlled-environment equipment

Construction & performance

Protected on both faces

Dual protective mesh helps shield the delicate filter medium during handling and installation. Carry the filter by its frame and avoid contact with the media.

Housing-compatible sealing

An inward-return aluminium frame and black gaskets on both faces provide a configurable sealing arrangement. Match the gasket contact surface and clamping method to the installation drawing.

Selection guide

How to choose.

01

Confirm the opening and frame profile

Send the installation drawing, opening dimensions and gasket contact area. Confirm whether the required overall depth includes the uncompressed gaskets.

02

Define airflow and resistance together

Specify rated airflow in m³/h and maximum acceptable initial pressure drop in Pa. A same-size filter can have a different resistance when the medium, pleat geometry or efficiency changes.

03

Confirm installation direction

Follow the airflow arrow or approved drawing. Two-sided mesh and gaskets do not mean that either flow direction is interchangeable.

04

Agree the test documentation

Specify H14 classification and the required efficiency and leak-test documentation for the delivered configuration.

Technical data

Specifications & dimensions.

Featured configuration
Overall dimensions1170 × 570 × 70 mm (long side × short side × frame depth)
Finished-filter gradeH14; EN 1822 class criterion: integral efficiency ≥ 99.995% at MPPS. Specify the required individual test report when ordering.
Filter mediumGlass fibre; supplied media reference: H13-1130. This reference is not the finished-filter efficiency class.
Pleat constructionMini-pleat / separator-free format
FrameAluminium with inward-return flange
Face protectionProtective mesh on both sides
SealingBlack gaskets on both sides; gasket material, thickness and compression to suit the housing
Rated airflow (m³/h)Selected for the application; provide required airflow for a matched quotation
Initial pressure drop (Pa)Specified at the agreed rated airflow for the selected media and pleat pack
Temperature / humidity limitsSpecify operating conditions; the assembled filter rating depends on media, adhesive, sealant and gaskets
Custom configurationsDimensions, filtration grade, frame material, filter medium, mesh and gasket configuration

Dimensions and construction describe the featured product. Airflow, pressure drop and operating limits are agreed for the ordered configuration.

FAQ

Common questions.

Is H13-1130 an H13 finished-filter rating?

No. H13-1130 is the glass-fibre media reference shown in the supplied product information. The featured finished-filter grade is H14; acceptance should follow the agreed test report.

Can the dimensions or materials be customised?

Yes. Different dimensions, filtration grades, frame materials and filter media can be discussed, together with protective mesh and gasket options.

Can this be treated as a high-temperature filter?

Do not infer the complete filter temperature rating from the glass fibre or aluminium alone. Provide the operating temperature and humidity so that the adhesive, sealant and gaskets can also be selected.

Beyond the catalogue

Your dimensions.
Your filtration requirements.

More models are available on enquiry. Tell us your target dimensions, model reference, media, frame, sealing and filtration requirements.

Discuss this configuration↗