Product overview
What it is and where it fits.
The AR207 V-Cell arranges eight mini-pleat glass-fibre panels into four V-shaped banks inside a 292 mm (12 in) deep frame. The V geometry adds media area for high airflow at a low pressure drop in the medium-efficiency stage of air handling units.
The catalogue describes face velocities up to 750 ft/min (3.81 m/s) and dust-spot grades of 60–65%, 80–85% and 90–95%. Frames can be ABS, galvanised steel, aluminium or stainless steel, with sealed panel-to-frame joints.
- Filter type
- Compact V-bank (V-Cell)
- Construction
- 8 mini-pleat panels in 4 V-banks
- Depth
- 292 mm (12 in)
- Dust-spot grades
- 60–65%, 80–85%, 90–95% (MERV 11–14)
- Initial pressure drop (catalogue)
- 63 / 79 / 100 Pa by grade; final 324 Pa
- Face velocity
- Up to 3.81 m/s (750 ft/min)
- Frames
- ABS, galvanised steel, aluminium, stainless steel
Typical applications
- Medium-efficiency stage in high-airflow air handling units
- Pre-HEPA filtration in cleanroom supply systems
- Replacing pocket filters where housing depth is limited
Construction & performance
V-bank construction
Eight mini-pleat panels form four V-shaped banks for high airflow and increased media area. The catalogue describes a 12-inch (292 mm) depth and face velocities up to 750 ft/min (3.81 m/s).
Materials & efficiency
Micro-glass fiber media with sealed panel-to-frame joints. ABS, galvanized steel, aluminum and stainless steel frames can be specified. Dust-spot grades: 60–65%, 80–85% and 90–95%.
Operating limits
The standard construction is rated as shown in the operating-condition table. High-temperature constructions are available on request.
Selection guide
How to choose.
V-Cell or pocket filter
A V-Cell is rigid, will not collapse at variable airflow and has a low pressure drop; a pocket filter is lighter and cheaper per unit.
Frame material
ABS frames are light and corrosion-free; metal frames suit high temperature or where a flange is required.
Technical data
Specifications & dimensions.
Rated airflow in m³/h, pressure drop in Pa, actual dimensions in mm, nominal sizes in inches. Swipe tables sideways on small screens.
| Dust-spot efficiency | Gravimetric efficiency | MERV |
|---|---|---|
| 90–95% | > 99% | 14 |
| 80–85% | > 98% | 13 |
| 60–65% | > 97% | 11 |
| Test standard: ASHRAE 52.1-1992 / EN 779 | MERV: ASHRAE 52.2 | |
| Efficiency (%) | Nominal size (in) | Actual size (mm) | Rated airflow (m³/h) | Pressure drop (Pa) | ||
|---|---|---|---|---|---|---|
| Dust-spot efficiency | Gravimetric efficiency | Initial pressure drop | Final pressure drop | |||
| 90–95 | > 99 | 12 × 24 × 12 | 289 × 595 × 292 | 1700 | 100 | 324 |
| 24 × 24 × 12 | 595 × 595 × 292 | 3400 | ||||
| 80–85 | > 98 | 12 × 24 × 12 | 289 × 595 × 292 | 1700 | 79 | 324 |
| 24 × 24 × 12 | 595 × 595 × 292 | 3400 | ||||
| 60–65 | > 97 | 12 × 24 × 12 | 289 × 595 × 292 | 1700 | 63 | 324 |
| 24 × 24 × 12 | 595 × 595 × 292 | 3400 | ||||
| Type | Specification | ||||
|---|---|---|---|---|---|
| Construction | Filter media | Micro-glass fiber paper | |||
| Support material | Corrugated separator | ||||
| Sealant | PU BASE | ||||
| Gasket material | Neoprene rubber | ||||
| Frame material | Metal frame | ABS frame | |||
| Frame type | Box type | Single flange | |||
| Operating conditions | Maximum temperature | ℃ | 60 | ||
| Maximum continuous temperature | ℃ | 40 | |||
| Maximum relative humidity | %RH | 100 (non-condensing) | |||
Catalogue values at rated airflow. Test data for your exact configuration is available on request.
Original Yiding catalogue (Chinese) ↗FAQ
Common questions.
What is a V-Cell filter?+
A rigid filter that arranges mini-pleat media panels in a V shape to fit a large media area into a compact frame, used for medium-efficiency filtration at high airflow.
What is the pressure drop?+
In the catalogue table, initial pressure drop is 63, 79 and 100 Pa for the 60–65%, 80–85% and 90–95% grades, with a final pressure drop of 324 Pa.