← All products

HVAC Filters / AR207

V-Cell Air Filter

Compact V-bank design for higher airflow.

Mini-pleat glass fiber media in a V-bank arrangement. Frame options include ABS and metal.

Standard models and custom dimensions available. Ask us to match your filtration requirements.

Product overview

What it is and where it fits.

The AR207 V-Cell arranges eight mini-pleat glass-fibre panels into four V-shaped banks inside a 292 mm (12 in) deep frame. The V geometry adds media area for high airflow at a low pressure drop in the medium-efficiency stage of air handling units.

The catalogue describes face velocities up to 750 ft/min (3.81 m/s) and dust-spot grades of 60–65%, 80–85% and 90–95%. Frames can be ABS, galvanised steel, aluminium or stainless steel, with sealed panel-to-frame joints.

Filter type
Compact V-bank (V-Cell)
Construction
8 mini-pleat panels in 4 V-banks
Depth
292 mm (12 in)
Dust-spot grades
60–65%, 80–85%, 90–95% (MERV 11–14)
Initial pressure drop (catalogue)
63 / 79 / 100 Pa by grade; final 324 Pa
Face velocity
Up to 3.81 m/s (750 ft/min)
Frames
ABS, galvanised steel, aluminium, stainless steel

Typical applications

  • Medium-efficiency stage in high-airflow air handling units
  • Pre-HEPA filtration in cleanroom supply systems
  • Replacing pocket filters where housing depth is limited

Construction & performance

V-bank construction

Eight mini-pleat panels form four V-shaped banks for high airflow and increased media area. The catalogue describes a 12-inch (292 mm) depth and face velocities up to 750 ft/min (3.81 m/s).

Materials & efficiency

Micro-glass fiber media with sealed panel-to-frame joints. ABS, galvanized steel, aluminum and stainless steel frames can be specified. Dust-spot grades: 60–65%, 80–85% and 90–95%.

Operating limits

The standard construction is rated as shown in the operating-condition table. High-temperature constructions are available on request.

Selection guide

How to choose.

01

V-Cell or pocket filter

A V-Cell is rigid, will not collapse at variable airflow and has a low pressure drop; a pocket filter is lighter and cheaper per unit.

02

Frame material

ABS frames are light and corrosion-free; metal frames suit high temperature or where a flange is required.

Technical data

Specifications & dimensions.

Rated airflow in m³/h, pressure drop in Pa, actual dimensions in mm, nominal sizes in inches. Swipe tables sideways on small screens.

Efficiency & test standard
Dust-spot efficiencyGravimetric efficiencyMERV
90–95%> 99%14
80–85%> 98%13
60–65%> 97%11
Test standard: ASHRAE 52.1-1992 / EN 779MERV: ASHRAE 52.2
Dimensions & performance
Efficiency
(%)
Nominal size
(in)
Actual size
(mm)
Rated airflow
(m³/h)
Pressure drop
(Pa)
Dust-spot efficiencyGravimetric efficiencyInitial pressure dropFinal pressure drop
90–95> 9912 × 24 × 12289 × 595 × 2921700100324
24 × 24 × 12595 × 595 × 2923400
80–85> 9812 × 24 × 12289 × 595 × 292170079324
24 × 24 × 12595 × 595 × 2923400
60–65> 9712 × 24 × 12289 × 595 × 292170063324
24 × 24 × 12595 × 595 × 2923400
Materials & operating conditions
TypeSpecification
ConstructionFilter mediaMicro-glass fiber paper
Support materialCorrugated separator
SealantPU BASE
Gasket materialNeoprene rubber
Frame materialMetal frameABS frame
Frame typeBox typeSingle flange
Operating conditionsMaximum temperature℃60
Maximum continuous temperature℃40
Maximum relative humidity%RH100 (non-condensing)

Catalogue values at rated airflow. Test data for your exact configuration is available on request.

Original Yiding catalogue (Chinese) ↗

FAQ

Common questions.

What is a V-Cell filter?

A rigid filter that arranges mini-pleat media panels in a V shape to fit a large media area into a compact frame, used for medium-efficiency filtration at high airflow.

What is the pressure drop?

In the catalogue table, initial pressure drop is 63, 79 and 100 Pa for the 60–65%, 80–85% and 90–95% grades, with a final pressure drop of 324 Pa.

Beyond the catalogue

Your dimensions.
Your filtration requirements.

More models are available on enquiry. Tell us your target dimensions, model reference, media, frame, sealing and filtration requirements.

Discuss this configuration↗