The AR206 P-Cell is a compact 4-inch (95 mm) deep mini-pleat panel filter for the medium-efficiency stage of air handling units, paint-booth intakes and prefiltration ahead of HEPA filters. Its pleats are held by adhesive beads rather than aluminium separators.

Water-resistant, dual-density glass-fibre paper and synthetic media options are described, with dust-spot efficiency grades of 60–65%, 80–85% and 90–95% (MERV 11, 13 and 14 in the catalogue).

Filter type
Mini-pleat panel (P-Cell)
Depth
95 mm (4 in)
Dust-spot grades
60–65%, 80–85%, 90–95%
MERV equivalent (catalogue)
MERV 11, 13, 14
Sizes
289×595 and 595×595 mm
Media
Glass-fibre paper or synthetic
Frames
Cardboard or metal; box or single flange
Described capacity
3,400 m³/h (2,000 CFM) for 24×24 in

Typical applications

  • Medium-efficiency stage in air handling units
  • Paint-booth intake filtration
  • Prefiltration ahead of HEPA filters
  • Upgrading 4-inch panel slots to higher efficiency

Construction & performance

Compact format

A 4-inch (95 mm) deep mini-pleat filter for air handling units, paint-booth intake and prefiltration ahead of high-efficiency filters. A 24 × 24 in (595 × 595 mm) filter is rated at 3,400 m³/h (2,000 CFM).

Media & frames

The catalogue describes water-resistant, dual-density glass fiber paper and synthetic media options. Pleats are adhesive-supported without aluminum separators. Cardboard and metal frames are available.

Efficiency options

Dust-spot efficiency grades: 60–65%, 80–85% and 90–95% under the catalogue’s ASHRAE 52.1-1992 reference.

Selection guide

How to choose.

01

Upgrade without changing the housing

A P-Cell fits the same 4-inch slot as a pleated panel filter while offering much higher efficiency grades.

02

Pick the grade by position

Use 90–95% ahead of HEPA filters; 60–65% or 80–85% for general supply air.

Technical data

Specifications & dimensions.

Rated airflow in m³/h, pressure drop in Pa, actual dimensions in mm, nominal sizes in inches. Swipe tables sideways on small screens.

Efficiency & test standard
Dust-spot efficiencyGravimetric efficiencyMERV
90–95%> 99%14
80–85%> 98%13
60–65%> 97%11
Test standard: ASHRAE 52.1-1992 / EN 779MERV: ASHRAE 52.2
Dimensions & performance
Efficiency
(%)
Nominal size
(in)
Actual size
(mm)
Rated airflow
(m³/h)
Pressure drop
(Pa)
Dust-spot efficiencyGravimetric efficiencyInitial pressure dropFinal pressure drop
90–95> 9912 × 24 × 4289 × 595 × 951700169324
24 × 24 × 4595 × 595 × 953400
80–85> 9812 × 24 × 4289 × 595 × 951700147324
24 × 24 × 4595 × 595 × 953400
60–65> 9712 × 24 × 4289 × 595 × 951700100324
24 × 24 × 4595 × 595 × 953400
Materials & operating conditions
TypeSpecification
ConstructionFilter mediaMicro-glass fiber filter paper
Support meshHot-melt adhesive
Frame materialMetal frame
Frame typeBox typeSingle flange
Operating conditionsMaximum temperature℃60
Maximum continuous temperature℃40
Maximum relative humidity%RH98 (non-condensing)

Catalogue values at rated airflow. Test data for your exact configuration is available on request.

Original Yiding catalogue (Chinese) ↗

FAQ

Common questions.

What is a P-Cell filter?

A compact mini-pleat panel filter, typically 4 inches deep, that gives medium-to-high efficiency in the space of a standard panel filter.

P-Cell or pocket filter?

Both serve the medium-efficiency stage. A P-Cell is rigid and only 95 mm deep; a pocket filter needs a deeper housing but usually holds more dust.

Beyond the catalogue

Your dimensions.
Your filtration requirements.

More models are available on enquiry. Tell us your target dimensions, model reference, media, frame, sealing and filtration requirements.