Product overview
What it is and where it fits.
The AR101 is a washable mesh prefilter for the first stage of an air handling system. Single- or double-layer PE, PP or nylon mesh is formed on a welded-wire support and finished with a stitched black plastic edge, so the filter can be cleaned and reused instead of replaced.
It stops coarse dust, fibres and insects at outdoor-air and return-air intakes and protects the medium-efficiency filters downstream. The catalogue lists gravimetric efficiency above 65% (ASHRAE 52.1) with a very low initial pressure drop.
- Filter type
- Washable mesh prefilter
- Media
- PE, PP or nylon mesh, single or double layer
- Gravimetric efficiency (catalogue)
- > 65%
- Thickness
- 22 mm (single) or 45 mm (double layer)
- Standard sizes
- 289 × 595 and 595 × 595 mm
- Initial / final pressure drop
- 26 / 50 Pa (single), 39 / 60 Pa (double)
- Support & frame
- Galvanised or stainless wire; optional steel, aluminium or stainless frame
- Max. continuous temperature
- 40 °C
Typical applications
- Outdoor-air intakes of air handling units
- Return-air prefiltration
- Protection of coils and fans from coarse dust and insects
- Industrial ventilation where filters are cleaned on site
Construction & performance
Design & maintenance
Single- or double-layer PE, PP or nylon mesh is formed on a welded-wire support with a stitched black plastic edge. The washable construction is easy to clean and maintain.
Media & frame options
Galvanized or stainless steel wire support; optional galvanized steel, aluminum or stainless steel outer frames.
Filtration performance
The catalogue lists gravimetric efficiency above 65% under ASHRAE 52.1-1992. Single- and double-layer sizes and pressure-drop values are listed below.
Selection guide
How to choose.
Single or double layer
The double-layer version collects more dust at a slightly higher pressure drop; the single layer suits low-resistance intakes.
Frame for the environment
Wire-only filters are lightest; add a galvanised, aluminium or stainless outer frame for rigidity or humid, corrosive sites.
Technical data
Specifications & dimensions.
Rated airflow in m³/h, pressure drop in Pa, actual dimensions in mm, nominal sizes in inches. Swipe tables sideways on small screens.
| Dust-spot efficiency | Gravimetric efficiency |
|---|---|
| — | > 65% |
| Test standard: ASHRAE 52.1-1992 / EN 779 | |
| Efficiency (%) | Nominal size (in) | Actual size (mm) | Rated airflow (m³/h) | Pressure drop (Pa) | ||
|---|---|---|---|---|---|---|
| Dust-spot efficiency | Gravimetric efficiency | Initial pressure drop | Final pressure drop | |||
| — | > 65 (single layer) | 12 × 24 × 1 | 289 × 595 × 22 | 1700 | 26 | 50 |
| 24 × 24 × 1 | 595 × 595 × 22 | 3400 | ||||
| — | > 65 (double layer) | 12 × 24 × 2 | 289 × 595 × 45 | 1700 | 39 | 60 |
| 24 × 24 × 2 | 595 × 595 × 45 | 3400 | ||||
| Type | Specification | ||
|---|---|---|---|
| Construction | Filter media | PE | |
| Frame material | Metal frame | ||
| Operating conditions | Maximum continuous temperature | ℃ | 40 |
| Maximum relative humidity | %RH | 98 (non-condensing) | |
Catalogue values at rated airflow. Test data for your exact configuration is available on request.
Original Yiding catalogue (Chinese) ↗FAQ
Common questions.
Can nylon mesh filters be washed?+
Yes. The mesh and wire support are designed to be cleaned with water or compressed air and reused. Let the filter dry before reinstalling it.
Where is a mesh prefilter used?+
At the very first stage — outdoor-air and return-air intakes — to stop coarse particles and insects so that the pleated, pocket and HEPA filters downstream last longer.