Technical Guides
2026-10-30
How to read Camfil Opakfil ES types ES6 to ES9, which ISO 16890 class and size each stands for, and how our V-Cell compact filter compares.
Key points
Opakfil ES is Camfil's compact V-filter for air handling units and for prefiltration ahead of cleanroom HEPA filters. Glass-fibre mini-pleat packs, held by hot-melt separators, are set in V-shapes inside a moulded ABS plastic frame. The front dimensions follow EN 15805 and the depth is 296 mm. The type code, ES6 to ES9, gives the efficiency class.
Our V-Cell filter uses the same layout: eight mini-pleat glass-fibre panels in four V-banks, in an ABS or metal frame.
| Opakfil type | EN 779 | ISO 16890 | Initial pressure drop at nominal airflow | Nearest Yiding V-Cell grade |
|---|---|---|---|---|
| ES6 | M6 | ePM10 70% | 60 Pa | 60–65% dust-spot (MERV 11) |
| ES7 | F7 | ePM1 60% | 65 Pa | 80–85% dust-spot (MERV 13) |
| ES8 | F8 | ePM1 70% | 75 Pa | 90–95% dust-spot (MERV 14) |
| ES9 | F9 | ePM1 80% | 90 Pa | 90–95% dust-spot (MERV 14) |
Our catalogue grades are dust-spot ratings (ASHRAE 52.1) and do not convert exactly to ISO 16890. When you order against an Opakfil type, we build to its ISO 16890 class and confirm it in the test report sent with the quote.
| Opakfil size W × H × D (mm) | Nominal airflow (m³/h) | Our V-Cell catalogue |
|---|---|---|
| 592 × 592 × 296 | 3400 | 595 × 595 × 292 mm, rated 3400 m³/h |
| 592 × 490 × 296 | 2800 | Built to order |
| 592 × 287 × 296 | 1700 | 289 × 595 × 292 mm, rated 1700 m³/h |
Our catalogue sizes follow the US 24 × 24 in and 12 × 24 in modules. When you order against an Opakfil code, we build to its EN 15805 face size and 296 mm depth.
Camfil and Opakfil are trademarks of Camfil AB. Yiding is not affiliated with Camfil. Opakfil ES data on this page comes from Camfil's published datasheet (2025-01-17) and is used only to identify the size and class to be matched.
It has the same V-bank construction and can be built to the same 592 mm face size and 296 mm depth, so it fits the same housings. Confirm the frame, header and gasket when you order.
No. It is a different manufacturer's filter built to the same dimensions and class, with performance shown in our own test report.
A V-filter is rigid and does not collapse when airflow varies or the fan stops, and it is shorter than most bag filters. A bag filter is lighter and usually costs less per unit.
Yes. The V-Cell can be supplied with a galvanised steel, aluminium or stainless steel frame, which also suits higher operating temperatures.