← All products

Cleanroom Filters / AR601

Room-Side Replaceable Filter Module

A ceiling filter housing with room-side access.

Anodized aluminum housing for ceiling grids and panel ceilings. Replace the filter from below while retaining the housing. HEPA and ULPA options are available.

Standard models and custom dimensions available. Ask us to match your filtration requirements.

Product overview

What it is and where it fits.

The AR601 is a ceiling terminal module in which the housing stays in place and only the filter is replaced — from inside the cleanroom. That shortens replacement work, avoids opening the ceiling void and reduces the material cost of each change.

The anodised aluminium extrusion housing fits ceiling grids and panel ceilings, with a painted steel top, 150 mm housing height and an 80 mm inlet collar. Mini-pleat micro-glass fibre filters are offered in HEPA grades (99.97 / 99.99% at 0.3 µm) and ULPA (99.999995% at 0.1–0.2 µm).

Unit type
Room-side replaceable terminal filter module
Housing sizes
570×570, 600×600, 570×1170, 600×1210 mm × 150 mm
Filter sizes
528×528, 558×558, 528×1128, 558×1168 mm × 80 mm
Filter grades
HEPA 99.97 / 99.99%; ULPA 99.999995%
Rated airflow (catalogue)
350 m³/h (2×2 ft), 800 m³/h (2×4 ft)
Inlet sizes
8, 10, 12, 14
Insulation option
PE, 10 or 25 mm
Housing
Anodised aluminium, 1.0 mm painted steel top

Typical applications

  • Cleanroom ceilings with ducted HEPA supply
  • Pharmaceutical and hospital clean areas where filters are changed often
  • Retrofits that keep existing ductwork

Construction & performance

Room-side service

An anodized aluminum extrusion housing fits ceiling-grid or panel-ceiling systems. Replace the filter from inside the room while retaining the housing to reduce replacement work and material cost.

Housing & options

Painted steel top (1.0 mm), housing height 150 mm excluding the inlet, inlet collar height 80 mm. Pleat depth, media efficiency, airflow and inlet size can be specified.

Filtration

Micro-glass fiber media with hot-melt pleat spacing. HEPA and ULPA options are available according to the required cleanroom application.

Selection guide

How to choose.

01

Room-side or disposable module

Room-side replaceable modules keep the housing and change only the filter; disposable modules (AR602) replace the whole unit. Choose room-side where changes are frequent or ceiling access is limited.

02

Match inlet and ceiling module

Tell us the duct size and ceiling grid module (570 or 600 mm family) so the housing and collar fit.

Technical data

Specifications & dimensions.

Rated airflow in m³/h, pressure drop in Pa, actual dimensions in mm, nominal sizes in inches. Swipe tables sideways on small screens.

Efficiency & test standard
Particle sizeEfficiency
0.3 µm95%
99.97%
99.99%
99.999%
0.1–0.2 µm≥ 99.999%
Test standard: EN 1822
Dimensions & performance
Efficiency
(%)
Housing size
(mm)
Filter size
(mm)
Rated airflow
(m³/h)
Initial pressure drop
(Pa)
Particle size
(µm)
99.97 / 99.99570 × 570 × 150528 × 528 × 803501000.3
600 × 600 × 150558 × 558 × 8088
570 × 1170 × 150528 × 1128 × 80800101
600 × 1210 × 150558 × 1168 × 8091
99.999995570 × 570 × 150528 × 528 × 803501040.1–0.2
600 × 600 × 150558 × 558 × 8092
570 × 1170 × 150528 × 1128 × 80800104
600 × 1210 × 150558 × 1168 × 8096
Materials & operating conditions
TypeSpecification
ConstructionFilter mediaMicro-glass fiber paper
Support materialHot-melt adhesive
SealantPU BASE
Gasket materialNeoprene rubber
Gasket positionNoneUpstreamDownstreamBoth sides
Frame typeDry seal
Frame materialAnodized aluminum frame
Protective mesh materialPainted expanded meshAnodized expanded mesh
Protective mesh positionNoneUpstreamDownstreamBoth sides
Inlet size8101214
Inlet height80
Insulation materialPE
Insulation thicknessNone1025
Operating conditionsMaximum continuous temperature℃60
Maximum relative humidity%RH100 (non-condensing)

Catalogue values at rated airflow. Test data for your exact configuration is available on request.

Original Yiding catalogue (Chinese) ↗

FAQ

Common questions.

What does room-side replaceable mean?

The filter is removed and installed from below, inside the cleanroom, without entering the ceiling void or disconnecting the duct.

Can the module be insulated?

Yes. PE insulation of 10 or 25 mm thickness can be specified on the housing.

Beyond the catalogue

Your dimensions.
Your filtration requirements.

More models are available on enquiry. Tell us your target dimensions, model reference, media, frame, sealing and filtration requirements.

Discuss this configuration↗